Voltage drop calculation tool

Calculates conductor voltage drop based on Ohm's law, supports single-phase and three-phase circuits

Input Parameters

Note: The distance entered here is a one-way distance, and the round trip needs to be multiplied by 2

Calculation formula

Single phase circuit: VD = 2 × I × L × ρ / A

Three-phase circuit: VD = √3 × I × L × ρ / A

Where: VD=voltage drop (V), I=current (A), L=length (m), ρ=resistivity, A=cross-sectional area (mm²)

Voltage drop reference standard

High quality (≤2%)
Good (2%-3%)
Warning (3%-5%)
Dangerous (>5%)

According to GB/T 12345-2008, voltage drop should generally not exceed 5% of the rated voltage.

Copper core wire carrying capacity reference

1 mm² 6A
1.5 mm² 10A
2.5 mm² 16A
4 mm² 25A
6 mm² 32A
10 mm² 50A

* Ampacity is a reference value when the ambient temperature is 30°C